Watch the performance indicators

The earliest sign of trouble is rarely a breakdown — it is a slowly rising approach temperature, higher fan motor current, uneven wetting of the fill, more drift at the discharge, or increasing make-up water demand. Log cold-water temperature, wet-bulb, fan speed, motor current and conductivity so trends are visible.

Compare readings at similar ambient conditions; a single hot-day number tells you very little.

A practical inspection rhythm

Monthly: fan vibration and bearing noise, rotating distribution header, spray coverage, basin level and float valve, visible drift. Quarterly: fan blades and hub bolts, motor current against nameplate, belt / gearbox condition, fill scale or deformation, drift eliminator gaps, FRP shell condition. Annually: full internal inspection, basin clean-out, water-treatment review and spare-parts planning.

Never high-pressure-wash soft PVC fill; collapsed flutes are a permanent performance loss.

Water treatment and winter

Keep a documented programme: biocide dosing, scale and corrosion inhibitors, conductivity-based blowdown, side-stream filtration where solids are high, and regular biofilm inspection. Good drift eliminators and no stagnant dead legs support the same hygiene objective.

In freezing climates, drain idle towers completely (sloped self-draining coils and air valves help), use approved glycol where draining is impossible, stage or stop spray pumps at low ambient temperature, and keep minimum coil flow during part-load operation.

Spare parts worth stocking

PVC fill blocks, drift eliminator sections, spray nozzles and rotary heads, distribution pipes, axial fan blades, motors, gear reducers / belts and seals, support fittings and brass float valves. Keeping a small kit turns an unplanned stoppage into a scheduled short shutdown.

We identify compatible components from photographs, nameplates or dimensions — including for towers supplied by other manufacturers — and can ship consolidated spare-parts kits with export packing.

Need this applied to your project?

Send your heat load, flow rate and design wet-bulb temperature for a technical proposal.

Request a Quote
Start a project

Talk to a cooling tower engineer

Technical selection, drawings and a quotation — usually within one business day.